CF-02-53- NFPA 70: Article 800 (communications) Covers wire connecting to telephone or other communications system (i.e. PoE network wiring, etc.) Outside wiring Separate at least 4 inches from power wires Surge protectors required for Aerial cable Grounding conductor...
CF-02-52- NFPA 70: Article 760 Requirements Power shall not be supplied through ground fault circuit interrupters Breaker durably marked to indicate fire circuit Cable shall be marked FPL- Power Limited Fire Alarm FPLR- Power Limited Fire Alarm Riser FPLP- Power...
CF-02-51- Wiring Methods Shall not strap, tape or attach to another conduit or raceway for support Plenum rated cable required within a Plenum Plenum or Riser rates cable required in Riser High voltage conductors and low voltage conductors may not be run in the same...
CF-02-50- Wiring Methods Separate by barrier from other classes Associated system wiring permitted with 1/4” minimum spacing between high voltage and low voltage conductors within the same enclosure (i.e. 120vac and 24vdc at a fire alarm relay) From different class...