CF-05-57- Interconnected with Dwelling Unit Fire Warning Equipment

CF-05-57- Interconnected with Dwelling Unit Fire Warning Equipment The activation of dwelling unit smoke alarms shall only be permitted to be displayed at the protected premises control unit and annunciators as supervisory signals Paragraph 23.8.3.2 permits, but does...

CF-05-56- Interconnected with Dwelling Unit Fire Warning Equipment

CF-05-56- Interconnected with Dwelling Unit Fire Warning Equipment A protected premises fire alarm system shall be permitted to be interconnected to a household fire alarm system(s) for the purpose of activating the notification appliances connected to the household...

CF-05-55- Combination Systems

CF-05-55- Combination Systems Signals from carbon monoxide detectors and carbon monoxide detection systems transmitted to a fire alarm system shall be indicated as a carbon monoxide alarm signal Exception: When in accordance with the building’s response plan,...

CF-05-54- Combination Systems

CF-05-54- Combination Systems If the AHJ determines that the information being displayed or annunciated on a combination system is excessive and is causing confusion and delayed response to a fire emergency, the AHJ shall be permitted to require that the display or...

CF-05-53- Combination Systems

CF-05-53- Combination Systems In combination systems, fire alarm signals shall be distinctive, clearly recognizable, and shall be indicated as follows in descending order of priority: Signals associated with life safety Signals associated with property protection...