CF-09-32 – Deficiency & Impairments The supervising station shall report to the AHJ any fire alarm system for which required monitoring has been terminated * The service provider shall report to the AHJ any fire alarm system that is out of service more than 8...
CF-09-42 –Maintenance System equipment shall be maintained in accordance with the manufacturer’s published instructions The frequency of cleaning of system equipment shall depend on the type of equipment and the local ambient conditions Cleaning should be done in...
CF-09-41 – Sensitivity Testing Use of the SENS-RDR is designed to “…assure that each smoke detector is within its listed and marked sensitivity range…” per NFPA 72. The SENS-RDR CANNOT, however, initiate a detector/sensor alarm. Sensitivity testing shall...
CF-09-40 – Sensitivity Testing To ensure that each smoke detector is within its listed and marked sensitivity range, it shall be tested using any of the following methods: Calibrated test method Manufacturer’s calibrated sensitivity test instrument Listed control...
CF-09-39 – Sensitivity Testing Sensitivity shall be checked within 1 year after installation. Sensitivity shall be checked every alternate year thereafter After the second required calibration test, if sensitivity tests indicate that the device has remained within its...