CF-07.25- Electrically Locked Doors If means of egress doors are unlocked by the fire alarm system, the unlocking function shall occur prior to, or concurrent with, activation of any public-mode notification appliances in the area(s) served by the normally locked...
CF-07.24- Electrically Locked Doors For all means of egress doors connected in accordance with 21.9.1 where fire alarm control unit batteries are used, they shall comply with 10.6.7 (FACU Secondary Power Requirements) Fire alarm control unit batteries shall not be...
CF-07.22- Door & Shutter Release All detection devices used for door and shutter hold-open release service shall be monitored for integrity Exception: Smoke detectors used only for door and shutter release and not for open area protection Magnetic door and...
CF-07.21- Smoke Control Station Where interconnected as a combination system, a fire fighter’s smoke control station (FSCS) shall be provided to perform manual control over the automatic operation of the system’s smoke control strategy Where interconnected as a...