CF-07.05- Dedicated Function FACU System-type smoke detectors located in elevator lobbies elevator hoist ways, and elevator machine rooms including machine space, control room, and control space used to initiate fire fighters’ service recall shall be connected to the...

CF-07.03- Elevator recall & Shunt trip System Connection

CF-07.03- Elevator recall & Shunt trip System Connection All initiating devices (smoke or heat detectors) used to initiate fire fighters’ service recall shall be connected to the building fire alarm system If there is a building FACU, then the elevator recall...

CF-07.02- Listing & Monitoring

CF-07-02- Listing & Monitoring A listed relay or other listed appliance used to initiate control of emergency control functions shall: be located within 3 ft. of the controlled circuit or appliance function within the voltage and current limitations of the fire...

CF-07.04- Dedicated Function FACU

CF-07-05- Listing & Monitoring In facilities without a building fire alarm system, initiating devices used to initiate fire fighters’ service recall shall be connected to a dedicated function fire alarm control unit that shall be designated as “elevator recall...

CF-07.01- Emergency Control Functions

CF-07-01- Emergency Control Functions Building, fire, and emergency control elements or systems that are initiated by the fire alarm or emergency communications system and either increase the level of life safety for occupants or control the spread of the harmful...