CF-03-077- Section 3-8 – Smoke Detectors for Door Release

CF-03-077- Section 3-8 – Smoke Detectors for Door Release Area detection installed in accordance with 17.7.3 is permitted to be used as long as area detection is provided on both sides of the doors to be closed Smoke detectors that are used exclusively for smoke...

CF-03-076- Partitions

CF-03-076- Partitions Where partitions extend to within 15% of the ceiling height, the spaces separated by the partitions shall be considered as separate...

CF-03-075- Detector Orientation

CF-03-075- Detector Orientation To minimize dust contamination, smoke detectors, where installed under raised floors, shall be mounted only in an orientation for which they have been...

CF-03-074- Locate Near Hazard

CF-03-074- Locate Near Hazard If the intent is to protect against a specific hazard, the detector(s) shall be permitted to be installed closer to the hazard in a position where the detector can intercept the smoke NFPA 72- 17.7.3.1.3 is generally cited when detectors...

CF-03-073- Smoke Detector Locations

CF-03-073- Smoke Detector Locations Spot-type smoke detectors shall be located on the ceiling or, if on a sidewall, between the ceiling and 12 in. down from the ceiling to the top of the detector [Note that the 4 in. prohibition still applies to heat-sensing fire...