CF-03-036- Remote Alarm Indication Where smoke detectors are installed in concealed locations more than 10 ft above the finished floor or where the detector’s indicator is not visible to responding personnel, the detectors shall be provided with remote...
CF-03-034- Compatibility All devices and appliances that receive their power from the initiating device circuit or signaling line circuit of a control unit shall be listed for use with the control unit. (example:2-wire smoke detectors) * Check the panel manufacture’s...