CF-04-56- Corridor Spacing Visible notification appliances shall be located not more than 15 ft. from the end of the corridor with a separation not greater than 100 ft. between appliances If there is an interruption of the concentrated viewing path, such as a fire...
CF-04-52- Irregular Area Wall Spacing If a room configuration is not square, the square room size that allows the entire room to be encompassed or allows the room to be subdivided into multiple squares shall be used Notice the dashed lines, representing imaginary...