CF-04-46- ADA (2010) Fire Alarm Requirements 215 Fire Alarm Systems 215.1 General. Where fire alarm systems provide audible alarm coverage, alarms shall comply with 215 EXCEPTION: In existing facilities, visible alarms shall not be required except where an existing...
CF-04-45- NFPA 72 Device Requirements The light output shall comply with the polar dispersion requirements of ANSI/UL 1971, Standard for Safety Signaling Devices for Hearing Impaired, or equivalent The flash rate shall not exceed two flashes per second (2 Hz) nor be...
CF-04-43- Pathway Survivability Two-way in-building wired emergency communications systems shall have a pathway survivability of Level 2 or Level 3 Where a two-way radio communications enhancement system is used in lieu of a two-way in-building wired emergency...
CF-04-42- Pathway Survivability Level 0 pathways shall not be required to have any provisions for pathway survivability Level 1 shall consist of pathways in buildings that are fully protected by an automatic sprinkler system Level 2 shall consist of one or more of the...