CF-04-30- Audible Notification Appliances

CF-04-30- Audible Notification Appliances Ceiling-mounted or recessed appliances shall be permitted Appliances that are an integral part of a smoke detector, smoke alarm, or other initiating device shall be located in accordance with the requirements for that device...

CF-04-29- Section 4-3 – Audible Notification Appliances

CF-04-29- Section 4-3 – Audible Notification Appliances If ceiling heights allow, wall-mounted appliances shall have their tops above the finished floors at heights of not less than 90 in. and below the finished ceilings at distances of not less than 6...

CF-04-28- 520 Hz Tone

CF-04-28- 520 Hz Tone Effective January 1, 2014, audible appliances provided for the sleeping areas to awaken occupants shall produce a low frequency alarm signal that complies with the following: 1) The alarm signal shall be a square wave or provide equivalent...

CF-04-27- Sleeping Areas

CF-04-27- Sleeping Areas If any barrier, such as a door, curtain, or retractable partition, is located between the notification appliance and the pillow, the sound pressure level shall be measured with the barrier placed between the appliance and the...

CF-04-26- Sleeping Areas

CF-04-26- Sleeping Areas Where audible appliances are installed to provide signals for sleeping areas, they shall have a sound level of at least 15 dB above the average ambient sound level or 5 dB above the maximum sound or a sound level of at least 75 dBA, whichever...