CF-08.05- Monitoring Required – IBC Fire alarm systems shall be monitored by an approved supervising station Exceptions: Single and multiple-station smoke alarms required by Section 907.2.10 Smoke detectors in Group I-3 occupancies Supervisory service is not...
CF-08.04- Types of Signals Alarm Signal A signal that results from the manual or automatic detection of an alarm condition Trouble Signal A signal that results from the detection of a system trouble Supervisory Signal A signal that results from the detection of a...
CF-08.03- Alarm Activation Actuation of alarm notification appliances or emergency voice communications, emergency control function interface devices, and annunciation at the protected premises shall occur within 10 seconds after the activation of an initiating...
CF-08.02- Software & Firmware Control A record of installed software and firmware version numbers shall be maintained at the location of the fire alarm control unit All software and firmware shall be protected from unauthorized changes A single change in the...
CF-08.01- Protected Premise System A protected premises fire alarm system is any fire alarm system located at the protected premises Where signals are transmitted to a communication center or supervising station, the protected premises fire alarm system also falls...