CF-07.10- Ambient Conditions Smoke detectors should not be installed in outdoor locations or locations that are open to the weather (such as unenclosed elevator lobbies in open parking structures), because such environments can exceed the parameters of the detector...
CF-07.09- Un-sprinklered Hoist Ways Smoke detectors shall not be installed in un-sprinklered elevator hoist ways unless they are installed to activate the elevator hoist way smoke relief...
CF-07.08- High Ceilings In high-ceiling areas, to achieve the desired initiation, such as for elevator recall and protection of fire alarm control units (FACUs), detection should be placed on the wall above and within 60 in. from the top of the elevator door(s) or...
CF-07.07- Lobby Detector Location A lobby smoke detector shall be located on the ceiling within 21 feet of the centerline of each elevator door within the elevator bank under control of the detector Exception: For lobby ceiling configurations exceeding 15 feet in...
CF-07.06- Device Capabilities Each initiating device used to initiate fire fighters’ service recall shall be capable of initiating elevator recall when all other devices on the same initiating device circuit have been manually or automatically placed in the alarm...